Installing
Electrical Grounds

shpslogo.jpg (6992 bytes)

[lesson title]

2-2. Installing Conductors. When installing circuit grounds, use Table 2-2 to determine the proper size of conductor based on the size of the fuse or circuit breaker used.

Table 2-2.  Minimum size equipment ground conductors for grounding raceway and equipment

Table 2-2.   Minimum size equipment ground conductors for grounding raceway and equipment

a.   Table 2-2, shows the minimum size ground conductor that can be used for grounding equipment or raceways. Each ground conductor in the table has the capacity to safely carry the current required to blow a fuse or trip a circuit breaker (Figure 2-7).

NOTE:   Grounding is installed to protect personnel Without the proper size ground conductor or with a broken or poorly installed ground conductor, you or someone else could become the ground conductor.

Figure 2-7.  Properly installed and faulty circuits

Figure 2-7.   Properly installed and faulty circuits

b.   In cable, such as nonmetallic sheathed cable, ground conductors can be built-in (Figure 2-8). Request cable with a ground conductor if you need a ground conductor. You do not need to worry about the size of the ground conductor in cable. However, when you pull conductors in conduit, you must select the proper size of ground conductor.

Figure 2-8.  Cable with built-in ground conductor

Figure 2-8.   Cable with built-in ground conductor

c.   The size of electrical conductors is expressed in American wire gauge (AWG). The gauge refers to the diameter of the conductor. In house (interior) wiring, the minimum size conductor allowed is No. 14 AWG. Using the AWG designation, the smaller the number, the larger the size or diameter of the conductor. For example, a No. 8 AWG conductor is larger in diameter than a No. 10 AWG conductor. Once the AWG size reaches 4/0 (spoken as 4 aught), the next larger conductor is 250 thousand circular mills (kcmil). At this point, the AWG designation reverses and the larger the number, the larger the conductor.

NOTE:   If the exact amperage is not shown in the appropriate table, always go to the next larger size conductor for safety.

d.   Use Table 2-2, andTable 2-3, to see the difference in conductor size between a current-carrying conductor and a ground conductor. A No. 8 moisture-resistant, thermal-plastic copper conductor can carry 40 amperes (Table 2-3); however, a ground conductor for a 40-ampere circuit must be No. 10 copper (Table 2-2). In large cables and conduit where individual conductors are used, the ground conductor or conductors are smaller than the current-carrying conductors.

Table 2-3.  Allowable ampacities of insulated conductors

Table 2-3.   Allowable ampacities of insulated conductors


Content provider: U.S. Army, David L. Heiserman
Publisher: SweetHaven Publishing Services

Copyright © 2005, SweetHaven Publishing Services
All Rights Reserved.

Revised: April 19, 2005